T5数据中心新标准|T5和T4数据中心区别

2020年8月3日00:29:05 发表评论

数据中心最高等级Tire 5最新标准如下:5级数据中心主要从数据中心的冷却系统,电力系统,网络运营商,数据中心安全,防水性,电力持续性和清洁性,7个方面论述Tire 5数据中心最新标准。

T5和T4数据中心区别

为了更好的说明Tire 5数据中心最新标准,以下论述方法是:T5数据中心与T4数据中心区别对比

冷却系统

T4T5
没有要求数据中心在没有水的情况下,也可以永久运行下去
没有要求数据中心外部设有空气污染物监测装置和具有防护应对能力
持续的降温系统持续的降温系统
多条关键性分配路径到数据楼层。每个系统都配有重要错误应对设备和关键分配路径
12小时容错和多余水备份系统12小时容错和多余水备份系统
Meets ASHRAE high and low temperature requirements 什么叫ASHRAE temp 下期专门做科普Meets ASHRAE high and low temperature requirements 什么叫ASHRAE temp 下期专门做科普
Capacity at ASHRAE N=20 dry bulb and maximum wet bulb 什么叫ASHRAE temp 下期专门做科普Capacity at ASHRAE N=20 dry bulb and extreme maximum wet bulb 什么叫ASHRAE temp 下期专门做科普
每个隔断含有刚刚好的备份能力装置的数每个隔断含有刚刚好的备份能力装置的数
If chilled water technology is used, the chiller capacity is calculated at ASHRAE maximum wet bulb temperatureIf chilled water technology is used, the chiller capacity is calculated at ASHRAE maximum wet bulb temperature
自动检测泄露,自动缓解所有管道和支架泄露。自动检测泄露,自动缓解所有管道和支架泄露。

电力系统

T4T5
没有即使在数据中心90%设备都要维护是,A和B电力系统也能正常工作。
没有Stored energy system configured in an N+1 下次普及N+1知识
没有储备能量系统都有检测装置
没有主要线路都配有UPS和次电源控制电路板检测系统
没有
三个独立的、功能齐全的位置控制和监控设施的备用发点装置分布在多个站点
没有多个站点位于变压装置控制中心的电路骨干网,监控三个独立的位置和每个功能齐全的站点。
Fault tolerant standby power generationFault tolerant standby power generation
Fault tolerant critical power pathFault tolerant critical power path
Fault tolerant station standby power path and switchgearFault tolerant standby power path and switchgear
Fault tolerant UPSFault tolerant UPS
Fault tolerant power paths from power sources to UPS input and mechanical loadsFault tolerant power paths from power sources to UPS input and mechanical loads
Fault tolerant power sources for ancillary building systemsFault tolerant power sources for ancillary building systems
12小时故障备份电源100小时故障备份电源
Dual, diverse power pathDual, diverse power path
Tie circuit breaker separation ensures maintaining one does not expose personnel to energized parts on the otherTie circuit breaker separation ensures maintaining one does not expose personnel to energized parts on the other
Each compartment contains no more than the number of redundant capacity componentsEach compartment contains no more than the number of redundant capacity components
Capacity at ASHRAE N=20 dry bulb, maximum wet bulb and altitude 下次普及 ASHRAE N=20Capacity at ASHRAE N=20 dry bulb,  maximum wet bulb and altitude 下次普及 ASHRAE N=20
Standby power has a continuous or unlimited runtime ratingStandby power has a continuous or unlimited runtime rating
UPS has sufficient stored energy capacity to sustain continuous availability until alternative energy source supports site operationsUPS has sufficient stored energy capacity to sustain continuous availability until alternative energy source supports site operations
UPS and switchgear is compartmentalizedUPS and switchgear is compartmentalized
Distribution circuit breaker separation prevents personnel exposure to energized parts during maintenanceDistribution circuit breaker separation prevents personnel exposure to energized parts during maintenance

网络运营商

T4T5
没有所有客户可以选择10家ISP运营商
没有6 facility entry vaults from at least two pathways
没有具备高防

数据中心安全

T4T5
没有每个服务器架都是安全的
没有进入重要资产和网络比如HVAC/Power/Network/Security 保证安全
没有以每秒15张图像的速度对服务区和入口进行监控、动作激活、视频监控,并至少保留90天
没有数据中心楼层上的每个分隔笼/房间都是独立安全的
没有房间或者cage设施有带照片的身份证出入控制,记录180天的出入时间/日期/用户
没有设施外墙无窗,由混凝土或类似的不易燃、不渗透的墙制成
没有外门在钢架中加固(例如,钢加劲),钢架完全填充灌浆,如果无人操作,则无可见铰链
没有数据中心至少有7'和18“的周界围栏,带3股带刺铁丝网,或类似的尖头,与房屋呈45度角,不受车辆或行人进出的影响
没有该设施的所有入口都有防人器出入控制
没有访问控制通过PIN/生物特征/两人完整性对每个徽章持有人进行身份验证
没有安全操作使用法律允许的最严格的物理安全执行工具
没有数据层上不允许有易燃材料
没有满足符合逻辑数据存储审计标准
没有访问控制程序控制进入操作区域的权限
没有该房地可维持庇护所的安全运作100小时
没有安全小组至少每半年根据设施既定的定量和定性威胁评估方法进行安全威胁评估。
没有无高风险周边设施(如高度易燃、易爆、危险品或核风险)

防水

T4T5
没有独立可以修复的或者可替换双房顶系统
没有数据中心位置:100年外没有发过洪水的地方
没有所有的冷却用水都在建筑表层外部。
没有公司管理人员签署的保证服务水平的声明和保证书

电力可持续性和节能性

T4T5
没有100%可再生能源供电
没有一定是本地的、新可再生能源供电能
没有Seasoned sector 12 month PUE trailing average of less than 1.3 下次普及

总结:T5数据中心在安全上,清洁能源使用上,防水,电力系统和制冷系统上,绝对是目前世界上最高标准。更多海外数据中心简介请点击:更多。了解更多coresite数据中心详情:请点击

发表评论

您必须才能发表评论!